3RV1041-4MA10
SIEMENS 3RV1041-4MA10 — Motor starter protector
Identify the right part for your application
Siemens SIRIUS 3RV10 motor starter protector 3RV1041-4MA10, size S3, CLASS 10, with screw terminals and no included auxiliary switches. Siemens IC 10 AO 2012 (printed page 7/10, PDF page 132) specifies rated current In 100 A, thermal overload setting 80 ... 100 A, instantaneous release 1235 A, and Icu 50 kA at 400 V AC. The 45 kW motor-power figure is an indicative selection value for a four-pole standard motor at 400 V AC and 50 Hz, not a universal motor rating. This historical document does not establish current availability, condition, price or warranty.
Rated Current In
100 A
Motor Power Guide At 400 V AC, 50 Hz
45 kW
Thermal Overload Release Setting Range
80 ... 100 A
Instantaneous Overcurrent Release
1235 A
Siemens SIRIUS 3RV10 motor starter protector 3RV1041-4MA10, size S3, CLASS 10, with screw terminals and no included auxiliary switches. Siemens IC 10 AO 2012 (printed page 7/10, PDF page 132) specifies rated current In 100 A, thermal overload setting 80 ... 100 A, instantaneous release 1235 A, and Icu 50 kA at 400 V AC. The 45 kW motor-power figure is an indicative selection value for a four-pole standard motor at 400 V AC and 50 Hz, not a universal motor rating. This historical document does not establish current availability, condition, price or warranty.