Motor Trips Overload Relay – Troubleshooting

Step-by-step diagnosis when overload relay trips. Mechanical vs electrical causes.

Symptom: Overload relay trips repeatedly

  1. 1

    Check motor current

    Measure phase currents with clamp meter under load. Unbalanced phases (>10% deviation) indicate winding fault or supply issue.

  2. 2

    Verify overload setting

    Overload must be set to motor nameplate full-load current (FLC). Incorrect setting causes nuisance trips.

  3. 3

    Inspect mechanical load

    Binding bearings, blocked fan, jammed conveyor increase current. Check coupling and driven equipment.

  4. 4

    Consider ambient temperature

    High ambient reduces overload trip time. Ensure adequate cooling and correct thermal class.