Skip to main content

Contactor Chattering or Buzzing

Contactor making noise: causes and remedies for AC coil hum and chatter.

Symptom: Contactor buzzes or chatters

  1. 1

    Check coil voltage

    Measure voltage at coil terminals. Low voltage (<0.85 Un) causes incomplete pull-in and chatter.

  2. 2

    Dirty contacts

    Carbon build-up on pole faces. Clean with contact cleaner. Replace if pitted or welded.

  3. 3

    Mechanical obstruction

    Foreign material or deformed armature. Inspect for debris. Replace contactor if damaged.

  4. 4

    Coil damage

    Partial short in coil causes hum. Measure coil resistance; compare to datasheet. Replace if out of spec.

Related products